Grounding of PLC Good grounding is an important condition for the safe and reliable operation of the programmable logic controller(Siemens 6ES5988-3NB41 SIMATIC S5 Fan, B&R X20BR9300 X2X Link Bus Receiver, Allen Bradley 1783-ETAP 3 PORT ETHERNET/IP Tap, Allen Bradley 2711P-RDT15C PanelView Plus Display Module ). It is best to use grounding devices for the programmable logic controller and strong electrical equipment. The cross-sectional area of the grounding wire should be greater than 2mm 2 . The distance should be less than 50m. Moreover, a single-point access to the grounding device is achieved in the entire programmable program controller system. In a power plant or substation, a grounding network is available. The control panels and automation components may be far apart. If they are grounded on the nearest grounding copper bar, the grounding current of the strong electrical equipment may cause a large potential difference between the two grounding points, which will interfere with the normal operation of the control system. Work. In order to prevent the cross-interference caused by the currents on the grounding wires of different signal loops, the internal grounding wires of the weak current signals must be connected in separate systems (for example, in units of control panels), and then lead to a certain point of the grounding network with wires of a specified area . , so as to realize the single- point grounding of the control system. Have interest in above parts? get in touch with Vivi (sh_plc@163.com).